Descripción Smart-UPS RT Tower/Rack Mount Uninterruptible Power Supply User Manual
Fabricantes APC 
Logotipo APC Logotipo



Hay una vista previa y un enlace de descarga de SURT7500XLJ (archivo pdf) en la parte inferior de esta página.


Total 21 Páginas

No Preview Available ! SURT7500XLJ Hoja de datos, Descripción, Manual

User Manual
English
APC Smart-UPS® RT
7500/10000 VA 200-240 VAC 6U
Tower/Rack Mount
Uninterruptible Power Supply
990-1216A 12/2003

1 page




SURT7500XLJ pdf
7. 230V model only: For three-phase input, set the Input Phase Selector switch (see C) to ‘3’. For
single-phase input, leave switch in default position of ‘1’.
XLT/XLJ MODELS (200/208V)
OUTPUT
INPUT
L1A
L2A
L1
L2
AB
XLI MODEL (220/230/240V)
OUTPUT
INPUT
L1A
N1
A
8. Switch the circuit breakers ON.
9. Check line voltages.
10. Replace the access panel.
3
L1
L2
L3
C
B
N

5 Page





SURT7500XLJ arduino
3: USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, WEB/SNMP CARD, OPTIONAL
SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.
FUNCTION
FACTORY
DEFAULT
USER SELECTABLE
CHOICES
DESCRIPTION
Automatic Self-Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
Every 14 days
(336 hours),
On Startup Only,
No Self-Test
Set the interval at which the
UPS will execute a self-test.
UPS ID
UPS_IDEN
Up to eight characters to
define the UPS
Uniquely identify the UPS, (i.e.
server name or location) for
network management purposes.
Date of Last Battery
Replacement
Minimum Capacity
Before Return from
Shutdown
Manufacture Date
0 percent
mm/dd/yy
0, 15, 25, 35, 50, 60, 75,
90 percent
Reset this date when you replace
the battery modules.
Specify the percentage to which
batteries will be charged
following a low-battery
shutdown before powering
connected equipment.
Alarm Delay After
Line Failure
5 second delay
5 second delay,
30 second delay,
At Low Battery,
Never
Mute ongoing alarms or disable
all alarms permanently.
Shutdown Delay
20 seconds
0, 20, 60, 120, 240, 480,
720, 960 seconds
Set the interval between the time
when the UPS receives a
shutdown command and the
actual shutdown.
Duration of
Low Battery Warning.
2 minutes
PowerChute
software provides
automatic,
unattended
shutdown when
approximately two
minutes of battery
runtime remains.
2, 5, 7, 10, 12, 15, 18,
20 minutes.
The low battery warning beeps
become continuous when two
minutes of runtime remains.
Change the warning interval to a
higher setting if the operating
system requires a longer interval
for shutdown.
Synchronized Turn-on 0 seconds
Delay
0, 20, 60, 120, 240, 480,
720, 960 seconds
Specify the time the UPS will
wait after the return of utility
power before turn-on (to avoid
branch circuit overloads).
9

11 Page







PáginasTotal 21 Páginas
PDF Descargar[ Datasheet SURT7500XLJ.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
SURT7500XLJSmart-UPS RT Tower/Rack Mount Uninterruptible Power Supply User ManualAPC
APC
SURT7500XLTSmart-UPS RT Tower/Rack Mount Uninterruptible Power Supply User ManualAPC
APC

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar