FCPS-24F(E)
24 Volt, 6 Amp Remote Power Supply
Section: Power Supplies/Accessories
GENERAL
The FireLite FCPS-24F(E) is a compact, cost-effective, 6-
amp remote power supply with battery charger. The FCPS-
24F(E) may be connected to any 12- or 24-volt Fire Alarm
Control Panel (FACP) or may stand alone. Primary appli-
cations include Notification Appliance (bell) Circuit (NAC)
expansion (to support ADA requirements) or auxiliary
power to support 24-volt system accessories. The FCPS
provides regulated and filtered 24 VDC power to four No-
tification Appliance Circuits (two Class A [Style Z] and two
Class B [Style Y] or four Class B only). Alternately, the four
outputs may be configured as any combination of reset-
table/non-resettable power outputs (optimal for powering
four-wire smoke detectors). The FCPS-24F(E) also con-
tains a battery charger capable of charging up to 7.0 Amp
Hour batteries.
FEATURES
Requires input trigger voltage of 9.0 - 32 VDC.
Contains two, fully-isolated input/control circuits (trig-
gered from FACP Notification Appliance Circuit [NAC
expander mode] or jumpered permanently on [stand-
alone mode]).
Two Class A (Style Z) or Class B (Style Y) Notification
Appliance Circuits (circuits 1 & 3).
Two additional NACs that may be individually configured
for Class B (Style Y) operation only (circuits 2 & 4).
6 Amp full load output (3 amps max./ckt.) in NAC ex-
pander mode (UL 864).
4 Amp continuous output in stand-alone mode (UL 1481).
In stand-alone mode, output power circuits may be con-
figured as resettable (reset line from FACP required) or
non-resettable.
Fully regulated and filtered power output (optimal for
powering four-wire smoke detectors, annunciators and
other system peripherals requiring regulated/filtered
power).
Fuseless, power-limited technology meets new UL power-
limiting requirements, effective May 1, 1995.
Normally closed trouble contact.
Fully supervised power supply, battery and Notification
Appliance Circuits.
Selectable earth fault detection.
AC trouble report selectable for immediate, 8 or 16 hour
delay.
Optional ammeter/voltmeter.
Works with virtually any UL 864 fire alarm control which
utilizes an industry-standard reverse-polarity notification
circuit.
S2424
S1287
(FCPS-24F
FCPS-24FE)
CS868
(FCPS-24F)
MEA
387-94-E
(FCPS-24F)
California
State Fire
Marshal
7315-0075:176
(FCPS-24F)
Self-contained in compact, lockable cabinet (15" [381
mm] H x 14.5" [368 mm] W x 2.75" [70 mm] D).
Includes integral battery charger capable of charging up
to 7.0 AH batteries.
Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.25 mm²) wire.
STANDARDS and CODES
The FCPS-24F complies with the following standards:
NFPA 72 National Fire Alarm Code.
UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
UL 1481 Power Supplies for Fire Alarm Systems
(stand-alone mode).
FireLite® Alarms is a Honeywell company.
This document is not intended to be used for installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticipate all
requirements. All specifications are subject to change without notice.
For more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472.
Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105.
DF-51401 07/13/04 Page 1 of 3
| |||
구 성 | 총 3 페이지수 | ||
다운로드 | [ FCPS-24F.PDF 데이터시트 ] |
당사 플랫폼은 키워드, 제품 이름 또는 부품 번호를 사용하여 검색할 수 있는 |
구매 문의 | 일반 IC 문의 : 샘플 및 소량 구매 ----------------------------------------------------------------------- IGBT, TR 모듈, SCR 및 다이오드 모듈을 포함한 광범위한 전력 반도체를 판매합니다. 전력 반도체 전문업체 상호 : 아이지 인터내셔날 사이트 방문 : [ 홈페이지 ] [ 블로그 1 ] [ 블로그 2 ] |
부품번호 | 상세설명 및 기능 | 제조사 |
FCPS-2404 | NAC Power Expander | Fire Lite |
FCPS-24E | Remote Power Supply | Fire Lite Alarms |
DataSheet.kr | 2020 | 연락처 | 링크모음 | 검색 | 사이트맵 |