DataSheet.es    


PDF AHR-B420 Data sheet ( Hoja de datos )

Número de pieza AHR-B420
Descripción AC/DC Current transducer
Fabricantes LEM 
Logotipo LEM Logotipo



Hay una vista previa y un enlace de descarga de AHR-B420 (archivo pdf) en la parte inferior de esta página.


Total 3 Páginas

No Preview Available ! AHR-B420 Hoja de datos, Descripción, Manual

AC/DC Current transducer AHR-B420
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement).
True r.m.s. 4-20 mA current output.
IPN = 500 .. 2000 A
Electrical data
Primary nominal
DC & AC current
IPN (At rms)
500
800
1000
1500
2000
Primary AC current
max. peak value 1)
IP (A)
2000
2500
2000
2500
3000
Output currentt
IOUT (mA DC)
4-20
4-20
4-20
4-20
4-20
R L Load resistance
VC Supply voltage
IC Current consumption
ISL Output current limitation
ÎP Overload capability (Ampere Turns)
Performance data
X
εL
IOE
TCIOE
TCG
tr
BW
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of IPN .. ± IPN)
Electrical offset current, TA = 25°C
Temperature coefficient of IOE ( 0 .. + 60 °C)
(- 40..+ 70 °C)
Temperature coefficient of G (% of reading)
Response time to 90% of IPN step
Frequency bandwidth (±1 dB)
General data
TA Ambient operating temperature
TS Ambient storage temperature
m Mass
IPxx Protection degree
Type
AHR 500 B420
AHR 800 B420
AHR 1000 B420
AHR 1500 B420
AHR 2000 B420
< 300
+ 20 .. 50 V DC
30 mA + IOUT
< 25
mA
30000
At
< ± 1 % of IPN
< ± 1.0 % of IPN
4 mA <±1.0 % of IPN
± 3.2
µA/K
± 6.4
µA/K
± 0.15 %/K
< 150
ms
DC 20 .. 6000Hz
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
Note :
1) The max. peak AC current is the highest peak level of the primary signal that is
taken into account for accurate true r.m.s. calculation. Yet the device is designed
for maximum continuous true r.m.s. value equal to IPN, whereas the output is limited
by the above specified output limitation.
Features
DC + distorted AC waveform currents
measurement
True r.m.s. output
Busbar or panel mounting
Split core type
Insulated plastic case recognized
according to UL94-V0.
Advantages
High isolation between primary and
secondary circuits
Eliminates insertion loss
Easy installation.
Applications
AC power supplies or Motors:
True r.m.s. current sensing - the most
accurate way to monitor power supply
or motor input power
VFD Controlled Loads:
VFD output current monitoring to
indicate how the motor and the
attached load are operating
SCRs or Switch-mode Rectifiers:
Accurate measurement of output
current
Renewable Energy Installations or
Backup Batteries:
Continuous condition minitoring
allowing automatic failure detection/
anticipation.
061012/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com

1 page





PáginasTotal 3 Páginas
PDF Descargar[ Datasheet AHR-B420.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
AHR-B420AC/DC Current transducerLEM
LEM

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar