Datasheet.kr   

MMI-6SF 데이터시트 PDF




Gamewell-FCI에서 제조한 전자 부품 MMI-6SF은 전자 산업 및 응용 분야에서
광범위하게 사용되는 반도체 소자입니다.


 

PDF 형식의 MMI-6SF 자료 제공

부품번호 MMI-6SF 기능
기능 Multi-Mod 6 zone interface module
제조업체 Gamewell-FCI
로고 Gamewell-FCI 로고


MMI-6SF 데이터시트 를 다운로드하여 반도체의 전기적 특성과 매개변수에 대해 알아보세요.



전체 2 페이지수

미리보기를 사용할 수 없습니다

MMI-6SF 데이터시트, 핀배열, 회로
www.DataSheet4U.com
Description
The Velociti™ Series, multi-mod six zone interface
module (MMI-6SF) provides six (6), Style B (Class
B) or three (3), Style D (Class A) supervised initiat-
ing device circuits (IDC) suitable for use with
U. L. Listed conventional 2-wire smoke detectors
as well as any normally open contact device.
The VelocitiTM Series use a communication proto-
col that substantially increases the speed of com-
munication between the sensors and certain FCI
analog addressable fire alarm controls. These de-
vices operate in a grouped fashion. If one of the
devices in the group has a status change, the
panel’s microprocessor stops the group poll and
concentrates on the single device. The net effect is
response speed up to five times greater than ear-
lier designs.
The MMI-6SF connects to the signaling line circuits
(SLC) of the FCI analog addressable series fire
alarm control panels. Each of the MMI-6SF initiat-
ing device circuits occupies its own address on the
system’s SLC allowing each to be fully programma-
ble in its control-by-event sequence of operation.
The address of the first initiating device circuit is
set with a pair of rotary dials. Each remaining cir-
cuit is automatically assigned to its own subse-
quent address. The MMI-6SF module includes an
address disable jumper matrix to allow a maximum
of two unused addresses to be turned off to free
these addresses for other purposes. An additional
pair of jumpers selects either Style B or Style D
circuit configurations.
Each circuit has its own status LED that flashes to
indicate proper polling and lights steadily when the
output has been activated.
VelocitiSeries
MMI-6SF
Multi-Mod Six Zone
Interface Module
MMI-6SF
Features
Each MMI-6SF module provides six (6), Style B
(Class B) or three (3), Style D (Class A) individually
addressable individually programmable initiating
device circuits.
Suitable for use with U. L. Listed, compatible 2-wire
conventional smoke sensors and normally open
contact devices.
Removable wiring terminal blocks allow ease of
installation and servicing terminal.
Blocks can accommodate 12 to 18 AWG wire.
Flexible jumper configuration feature allowing
one or two monitoring circuit addresses to be disabled.
Individual LED indicators*.
Ideal for retrofit applications.
As many as thirty-six (36), initiating device circuits in
one 12” x 24” x 6.5” cabinet.
Two (2), mounting cabinets available for two (2),
(MBB-2 cabinet) to six (6), (MBB-6 cabinet) units.
Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm.*
Note: *Only the red LED is operative in panels that do not oper-
ate in Velociti™ mode.
An ISO 9001-2000 Company
Velocitiand E3 Seriesare trademarks of Fire Control Instruments.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2006 Gamewell-FCI. All rights reserved.
www.gamewell.fci.com
9020-0633 Rev. B page 1 of 2





구       성 총 2 페이지수
다운로드[ MMI-6SF.PDF 데이터시트 ]

당사 플랫폼은 키워드, 제품 이름 또는 부품 번호를 사용하여 검색할 수 있는

포괄적인 데이터시트를 제공합니다.


구매 문의
일반 IC 문의 : 샘플 및 소량 구매
-----------------------------------------------------------------------

IGBT, TR 모듈, SCR 및 다이오드 모듈을 포함한
광범위한 전력 반도체를 판매합니다.

전력 반도체 전문업체

상호 : 아이지 인터내셔날

사이트 방문 :     [ 홈페이지 ]     [ 블로그 1 ]     [ 블로그 2 ]



관련 데이터시트

부품번호상세설명 및 기능제조사
MMI-6SF

Multi-Mod 6 zone interface module

Gamewell-FCI
Gamewell-FCI

DataSheet.kr       |      2020   |     연락처      |     링크모음      |      검색     |      사이트맵