DataSheet.es    


PDF HPS3KW-NNR-032 Data sheet ( Hoja de datos )

Número de pieza HPS3KW-NNR-032
Descripción AC-DC / Distributed Power Front End 3U
Fabricantes Emerson 
Logotipo Emerson Logotipo



Hay una vista previa y un enlace de descarga de HPS3KW-NNR-032 (archivo pdf) en la parte inferior de esta página.


Total 3 Páginas

No Preview Available ! HPS3KW-NNR-032 Hoja de datos, Descripción, Manual

3000 Watts
HPS3KW
Total Power:
Input Voltage:
# of Outputs:
3000 Watts
180-264 VAC
Single
Special Features - *Module only
• Active Power Factor Correction
• EN61000-3-2 Harmonic Compliance
• Remote INHIBIT
• Single Wire Parallel
• Built-in EMI Filter
• Low Output Ripple
• +5V standby Output
• Built-in Cooling Fans
• Over Current Protection
• Over Voltage Protection
• Over Temperature Protection
• Hot Swap
• Built-in OR'ing Diodes
Environmental - *Module only
Operating Temperature: +5°C to 40°C
Non-Operating Temperature: -40° to +70°C
Electromagnetic Susceptibility: Designed to meet
EN61000-4-2, -4-3, 4-4, -4-5 Level 3
Humidity: 5 to 95% RH, non-condensing
Operating: Sinusoidal Vibration - 0.25G zero to peak,
10 to 500Hz, 0.25 oct/min in each three mutually
perpendicular axes. Random vibration - 0.002 G2/Hz,
10 to 500Hz, nominal 1G rms.
Non-operating: Sinusoidal Vibration - 0.75G zero to
peak, 10 to 500Hz, 0.50 oct/min in each three mutually
perpendicular axes. Random vibration - 0.008 G2/Hz,
10 to 500Hz, nominal 2G rms.
MTBF (demonstrated): >500KHrs at full load, 40°C
Electrical Specs - *Module only
Input
Input Range
Frequency
Inrush Current
Efficiency
EMI Filter
Power Factor
Leakage Current
180-264VAC
47 - 63 Hz
100A (peak)
85% typical at full load
CISPR22 Class A
0.98 typical
1.16 mA @ 240 VAC
Output
DC Voltage
Adjustment Range
Supervisory Output
Hold Up Time
Over Current
Over Voltage
Logic Control
ENABLE
AC OK
POWER FAIL
POWER GOOD
51.4V @ 57A*
5Vsb @ 5A
± 5%
5V @ 5A
20ms
51.4V: 110% - 150%
5Vsb: 101% - 125%
60V Max
Requires contact closure from
"PSON" to 5Vsb return.
TTL signal LOW
TTL signal LOW;
goes HIGH inthe event of failure
TTL logic signal goes high 100-
1000 msec after 48VDC output. It
goes LOW at least 1ms before loss
of regulation.
*10% Minimum load required.
Safety - *Module only
UL 60950 (UL Recognized)
NEMKO EN60950
TUV EN60950
CE Mark
1 Americas: 1-888-41-ASTEC
Europe (UK): 44 (1384) 842-211 Asia (HK): 852-2437-9662
rev 08.29.05

1 page





PáginasTotal 3 Páginas
PDF Descargar[ Datasheet HPS3KW-NNR-032.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
HPS3KW-NNR-032AC-DC / Distributed Power Front End 3UEmerson
Emerson
HPS3KW-NNR-032AC-DC / Distributed Power Front End 3UEmerson
Emerson

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar