부품번호 | 259.75 기능 |
|
|
기능 | Hazardous Area Fuses | ||
제조업체 | Littelfuse | ||
로고 | |||
전체 1 페이지수
Hazardous Area Fuses
Next
Previous
Barrier Network Fuse 242 Series
• Meets Barrier Network Standards (EN50020) for hazardous applications.
• High interrupting rating. Meets the 1500A minimum.
• Available in both axial lead and surface mount.
ELECTRICAL CHARACTERISTICS:
% of Ampere Rating
Opening Time
110%
4 hours, Minimum
300%
10 seconds, Maximum
1000%
0.002 seconds, Maximum
INTERRUPTING RATINGS: 4000 amperes at 250VAC/VDC
PACKAGING (500 pcs): For surface mount version add packaging suf-
fix UR. For Axial Leaded version add packaging suffix UA. For Axial
Leaded version, taped add packaging suffix UAT1.
ORDERING INFORMATION:
Catalog
Number
0242.050
0242.080
0242.100
0242.160
0242.200
0242.250
Ampere
Rating
.050
.080
.100
.160
.200
.250
Color
Coding
Red
Green
Blue
Violet
Brown
Black
Nominal
Resistance
Cold Ohms
11.34
8.19
3.60
3.00
2.68
1.6
Nominal
Melting I2t
A2 Sec.
0.000103
0.000214
0.000977
0.00157
0.0038
0.00579
Safe-T-Plus Fuse 259 Series
• Designed to allow equipment to meet “Intrinsically Safe” certification for
applications in gas plants, petrochemical and processing industries
where there is a danger of gas explosion from faulty circuits.
• Hermetically sealed.
ELECTRICAL CHARACTERISTICS:
% of Ampere Rating
Opening Time
100%
4 hours, Minimum
200%
5 seconds, Maximum
AGENCY APPROVALS: Meets CENELEC EN500014 to 039 and
IEC 60079-11.
INTERRUPTING RATINGS:
50 amperes at 125 VAC
300 amperes at 125 VDC
ORDERING INFORMATION:
Catalog
Number
0259.062
0259.125
0259.250
0259.375
0259.500
0259.750
0259001.
Ampere
Rating
.062
.125
.250
.375
.500
.750
1
Voltage
Drop
2.1
1.3
0.83
0.81
0.78
0.23
0.24
Maximum
Resistance
Cold Ohms
8.1
2.4
0.87
0.46
0.32
0.19
0.14
Nominal
Melting I2t
A2 Sec.
0.00016
0.0012
0.0095
0.025
0.07
0.062
0.01
Schedule of limitations.
1) The fuse must be so mounted that creepage and clearance distances meet the requirements
of Table 2 of EN50020 :1977 or Table 4 of EN50020 :1994 (equivalent to IEC 60079-11 4th
Edition 1999).
2) When used in intrinsically safe apparatus it will be necessary to determine a surface
temperature classification for the fuse.
3.02mm
(.119")
1.90mm
4.60mm (.075")
(.181")
8.40mm
(.331")
.635mm
(.025")
3.02mm
(.119")
1.90mm
4.60mm (.075")
(.181")
8.40mm
(.331")
(.512")
13mm
(.025")
.635mm
(.394")
10mm
(.315")
8mm
(.197")
5mm
326 w w w . l i t t e l f u s e . c o m
| |||
구 성 | 총 1 페이지수 | ||
다운로드 | [ 259.75.PDF 데이터시트 ] |
당사 플랫폼은 키워드, 제품 이름 또는 부품 번호를 사용하여 검색할 수 있는 |
구매 문의 | 일반 IC 문의 : 샘플 및 소량 구매 ----------------------------------------------------------------------- IGBT, TR 모듈, SCR 및 다이오드 모듈을 포함한 광범위한 전력 반도체를 판매합니다. 전력 반도체 전문업체 상호 : 아이지 인터내셔날 사이트 방문 : [ 홈페이지 ] [ 블로그 1 ] [ 블로그 2 ] |
부품번호 | 상세설명 및 기능 | 제조사 |
259.75 | Hazardous Area Fuses | Littelfuse |
259.75 | Hazardous Area Fuses | Littelfuse |
DataSheet.kr | 2020 | 연락처 | 링크모음 | 검색 | 사이트맵 |